Table 693: Binary inputs
Description Value
Operating range ±20% of the rated voltage
Rated voltage 24...250 V DC
Current drain 1.6...1.9 mA
Power consumption 31.0...570.0 mW
Threshold voltage 18...176 V DC
Reaction time 3 ms
Table 694: RTD/mA inputs
Description Value
RTD inputs Supported RTD
sensors
100 Ω platinum
250 Ω platinum
100 Ω nickel
120 Ω nickel
250 Ω nickel
10 Ω copper
TCR 0.00385 (DIN 43760)
TCR 0.00385
TCR 0.00618 (DIN 43760)
TCR 0.00618
TCR 0.00618
TCR 0.00427
Supported
resistance range 0...2 kΩ
Maximum lead
resistance (three-
wire
measurement) 25 Ω per lead
Isolation 2 kV (inputs to protective earth)
Response time <4 s
RTD/resistance
sensing current Maximum 0.33 mA rms
Operation
accuracy
Resistance Temperature
± 2.0% or ±1 Ω ±1°C
10 Ω copper: ±2°C
mA inputs Supported
current range 0…20 mA
Current input
impedance 44 Ω ± 0.1%
Operation
accuracy ±0.5% or ±0.01 mA
Table 695: Signal output X100: SO1
Description
Value
Rated voltage 250 V AC/DC
Continuous contact carry 5 A
Make and carry for 3.0 s 15 A
Make and carry for 0.5 s 30 A
Breaking capacity when the control-circuit time
constant L/R<40 ms
1 A/0.25 A/0.15 A
Minimum contact load 100 mA at 24 V AC/DC
1YHT530004D05 D Section 14
Technical data
615 series 873
Technical Manual

Table of Contents