EasyManua.ls Logo

ABB REF 545 - Page 53

ABB REF 545
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1MRS750527-MUM
REF 54_
53
Feeder Terminal
Technical Reference Manual, General
1) These ranges are supported only in the feeder terminal revisions of Release 2.5 or later.
Table 5.1.9.2-1 Measurement ranges
Parameter Values Default
Voltage range 0 = 0...1V 0...1 V
1 = 0...5 V
2 = 1...5 V
3 = 0...10 V
4 = 2...10 V
5 = -5...5 V
6 = -10...10 V
Current range 0 = 0...1 mA 0...1 mA
1 = 0...5 mA
2 = 1...5 mA
3 = 0...10 mA
4 = 0...20 mA
5 = 4...20 mA
6 = -1...1 mA
7 = -2.5...2.5 mA
8 = -5...5 mA
9 = -10...10 mA
10 = -20...20 mA
Resistance range 0 = 0...100 Ω 0...100 Ω
1 = 0...200 Ω
2 = 0...500 Ω
3 = 0...1000 Ω
4 = 0...2000 Ω
5 = 0...5000 Ω
6 = 0...10000 Ω
Temperature
range
0 = Pt100 -45...150 °C Pt100 -45...150 °C
1 = Pt100 -45...600 °C
2 = Pt250 -45...150 °C
3 = Pt250 -45...600 °C
4 = Pt1000 -45...150 °C
5 = Pt1000 -45...600 °C
6 = Ni100 -45...150 °C
7 = Ni100 -45...250 °C
8 = Ni120 -45...150 °C
9 = Ni120 -45...250 °C
10 = Ni250 -45...150 °C
11 = Ni250 -45...250 °C
12 = Ni1000 -45...150 °C
13 = Ni1000 -45...250 °C
14 = Cu10 -45...150 °C
15 = Ni120US -45..150 °C
1)
16 = Ni120US -45..250 °C
1)

Table of Contents