REG 316*4 1MRB520049-Uen / Rev. F ABB Switzerland Ltd
3-173
Alternative 2: Modification for cosj
GN
Settings:
Reference power
P
UI
P
S
N
NN
GN
GN
GN
´
== =
cos .j 08
Reverse power:
P
P
UI
UI
N
GN GN
NN
=
´
´
=
´
´
=0005 0005
13 8 4
14 4 5
0004
11
..
.
.
.
Alternative 3: Modification for j
GN
and c.t./v.t.. data
Settings:
Rated power
P
UI
UI
UI
N
NN
GN GN
NN
GN
=
´
´
=
´
´
´=
11
13 8 4
14 4 5
08 0614cos
.
.
..
j
Reverse power
P
P
N
= 0005.
Characteristic angle
The power function is connected to the phase currents and a
phase-to-neutral or phase-to-phase voltage. The purpose of the
phase compensation is twofold:
· to compensate the phase difference between the phase volt-
age and the any measured phase-to-phase voltage
· to determine whether the function responds to active or re-
active power.
The following table summarises the most important operating
modes to
simplify setting the corresponding parameters correctly.
The angles given apply for connection according to the connec-
tions in Index 12.
The phase compensation also provides facility for changing the
direction of measurement or to compensate incorrect v.t. or c.t.
polarity.