ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-180
D. Overload function settings - OLoad-Stator
Summary of parameters:
Text Unit Default Min. Max. Step
ParSet 4..1 P1
(
Select
)
Trip 00000000
k1-Setting s 041.4 1.0 120.0 0.1
I-Start IB 1.10 1.00 1.60 0.01
t-min s 0010.0 1.0 120.0 0.1
tg s 0120.0 10.0 2000.0 10.0
t-max s 0300.0 100.0 2000.0 10.0
t-Reset s 0120.0 10.0 2000.0 10.0
NrOfPhases 3 1 3 2
CurrentInp AnalogAddr 0
IB-Setting IN 1.00 0.50 2.50 0.01
BlockInp BinaryAddr F
Trip SignalAddr ER
Start SignalAddr ER
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
defines the tripping channel activated by the tripping output of
the function (tripping logic).
k1-Setting
Multiplier. Operating characteristic constant.
I-Start
Enabling current for operating characteristic.
t-min
Minimum operating time. Operating characteristic constant.
tg
Time during which the inverse characteristic is active. Oper-
ating characteristic constant.
This must not exceed the maximum delay time.