ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-184
Example:
t = 5 min or 300 s
DJ
m
= 70 K
DJ
n
= 60 K
k1 = 300
70 60
60
-
= 50 s
Typical settings:
IB-Setting according to protected unit
I-Start 1.1 IB
k1-Setting 41.4 s
t-min 10.0 s
tg 120.0 s
t-max 300.0 s
t-Reset 120.0 s