ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-202
D. Overfluxing function settings - Overexcitat
Summary of parameters:
Text Unit Default Min. Max. Step
ParSet 4..1 P1 (Select)
Trip 00000000
Delay s 01.00 0.10 60.00 0.01
VoltageInp CT/VT-Addr 0
V/f-Setting UN/fN 01.20 0.20 2.00 0.01
MaxMin MAX (Select)
BlockInp BinaryAddr F
Trip SignalAddr ER
Start SignalAddr
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
defines the tripping channel activated by the tripping output of
the function (tripping logic).
Delay
time delay between pick-up and tripping.
VoltageInp
defines the v.t. input channel.
All voltage inputs may be selected.
V/f-Setting
Setting of the voltage/frequency ratio for tripping.
MaxMin
defines operation as overfluxing or underfluxing. Settings:
MAX: overfluxing
MIN: underfluxing.