ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-230
D. Stator ground fault settings - Stator-EFP
Summary of parameters:
Text Unit Default Min. Max. Step
ParSet 4..1 P1 (Select)
Trip 000000
Alarm-Delay s 0.5 0.20 60.00 0.01
Trip-Delay s 0.5 0.20 60.00 0.01
RFsAlarmVal
k
W
10.0 0.1 20.0 0.1
RFsTripVal
k
W
1.0 0.1 20.0 0.1
REs
k
W
1.00 0.80 5.00 0.01
REs-2.Starpt
k
W
1.00 0.90 5.00 0.01
RFs-Adjust
k
W
10.0 8.000 12.00 0.01
MTransRatio 100.0 10.0 200.0 0.1
NrOfStarpt 1 1 2 1
VoltageInpUi
CT/VT-Addr.
0
*)
VoltageInpUs
CT/VT-Addr.
0
*)
2.StarptInp BinaryAddr F
AdjMTRInp BinaryAddr F
AdjREsInp BinaryAddr F
BlockInp BinaryAddr F
Trip SignalAddr ER
StartTrip SignalAddr
Alarm SignalAddr ER
StartAlarm SignalAddr
InterruptInt. SignalAddr
InterruptExt. SignalAddr
2.Starpt. SignalAddr
MTR-Adjust SignalAddr
REs-Adjust SignalAddr
Extern-Block SignalAddr
*)
REG 316*4 requires an input transformer unit Type 316GW61 K67 assigned to the following
voltage input channels:
VoltageInpUi: Channel 8
VoltageInpUs: Channel 9