ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-252
D. Rotor ground fault settings - Rotor-EFP
Summary of parameters:
Text Unit Default Min. Max. Step
ParSet 4..1 P1 (Select)
Trip 00000000
Alarm-Delay s 0.50 0.20 60.00 0.01
Trip-Delay s 0.50 0.20 60.00 0.01
RFrAlarmVal
k
W
10.0 0.1 25.0 0.1
RFrTripVal
k
W
1.0 0.1 25.0 0.1
REr
k
W
1.00 0.90 5.00 0.01
Uir V 50 (Select)
RFr-Adjust
k
W
10.0 8.000 12.00 0.01
CouplingCap µF 4.00 2.00 10.00 0.01
VoltageInpUi CT/VT-Addr.
0
*)
VoltageInpUr CT/VT-Addr.
0
*)
AdjRErInp BinaryAddr F
AdjCoupCInp BinaryAddr F
BlockInp BinaryAddr F
Trip SignalAddr ER
StartTrip SignalAddr
Alarm SignalAddr ER
StartAlarm SignalAddr
InterruptInt SignalAddr
InterruptExt SignalAddr
REr-Adjust SignalAddr
CoupC-Adjust SignalAddr
Extern-Block SignalAddr
*)
REG 316*4 requires an input transformer unit Type 316GW61 K67 assigned to the following
voltage input channels:
VoltageInpUi: Channel 8
VoltageInpUr: Channel 7.