ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-260
D. Pole slip settings - Pole-Slip
Summary of parameters:
Text Unit Default Min. Max. Step
ParSet 4..1 P1 (Select)
Trip1 00000000
ZA UN / IN 0,00 0,000 5,000 0,001
ZB UN / IN 0,00 -5,000 0,000 0,001
ZC UN / IN 0,00 0,000 5,000 0,001
Phi deg 090 60 270 1
WarnAngle deg 000 0 180 1
TripAngle deg 090 0 180 1
n1 1 0 20 1
n2 1 0 20 1
t-Reset s 5,000 0,500 25,000 0,010
CurrentInp AnalogAddr 0
VoltageInp AnalogAddr 0
BlockGen BinaryAddr F
BlockMot BinaryAddr F
BlockInp BinaryAddr F
EnableZone1 BinaryAddr F
Warning SignalAddr ER
Generator SignalAddr ER
Motor SignalAddr ER
Zone1 SignalAddr ER
Zone2 SignalAddr ER
Trip1 SignalAddr ER
Trip2 SignalAddr ER
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).