ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-302
D. Logic function settings - Logic
Summary of parameters:
Text Units Default Min. Max. Step
ParSet 4..1 P1 (Select)
Trip 00000000
Logic Mode OR (Select)
BinOutput SignalAddr ER
BlockInp BinaryAddr F
BinInp1 (R1) BinaryAddr F
BinInp2 (R2) BinaryAddr F
BinInp3 (S1) BinaryAddr F
BinInp4 (S2) BinaryAddr F
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
Definition of the tripping circuit excited by the function’s O/P
(tripping matrix).
Logic Mode
Definition of the logic function to be performed by the 4 binary
I/P’s. Possible settings:
· OR: OR gate with all 4 binary I/P’s
· AND: AND gate with all 4 binary I/P’s
· R/S flip-flop: Flip-flop with 2 set I/P’s (S1 and S2) and 2
reset I/P’s (R1 and R2). The O/P is set or
reset when at least one of the corresponding
I/P’s is at logical “1” (OR gate).
Reset I/P’s take priority over the set I/P’s.
BinOutput
Output for signalling a trip.