D. Delay/integrator function settings - Delay
Summary of parameters:
Text Units Default Min. Max. Step
ParSet 4..1 P1 (Select)
Trip 00000000
Trip-Delay s 01.00 00.00 300.00 0.01
Reset-Delay s 00.01 00.00 300.00 0.01
Integration 0/1 0 0 1 1
BinaryInp BinaryAddr F
BlockInp BinaryAddr F
Trip SignalAddr ER
Start SignalAddr ER
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
Definition of the tripping logic (matrix) excited by the
function's output.
Trip-Delay
Time between start signal at the input and the tripping signal
at the output.
Reset-Delay
Time required for the timer to reset after the input signal has
disappeared.
Integration
Determination of the response of the function in the presence
of a pulsating I/P signal:
0: The delay continues to run, providing the I/P signal does
not disappear for longer than the reset time (see Fig.
3.6.3.1).
1: The time during which the I/P is at logical "1" is inte-
grated, i.e. tripping does not take place until the sum of
logical "1" time equals the set delay time (see Fig. 3.6.3.2).