ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-316
D. LDU event function settings – LDUevents
Summary of parameters:
Text Unit Default Min. Max. Step
ParSet 4..1 P1 (Select)
Trip 000000000
BlockInp BinaryAddr F
BinInput1 BinaryAddr F
BinInput2 BinaryAddr F
BinInput3 BinaryAddr F
BinInput 4 BinaryAddr F
BinOutput1 SignalAddr ER
BinOutput2 SignalAddr ER
BinOutput3 SignalAddr ER
BinOutput4 SignalAddr ER
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
Does not perform any function, always “0”.
BlockInp
Binary address used as blocking input.
F: - not used
xx: - all binary inputs (or outputs of a protection
function).
All outputs at logical “0” when the blocking input is active.
BinInput1, BinInput2, BinInput3, BinInput4
Binary inputs 1 to 4: Every input acts directly on the corre-
sponding output and can only be influenced by the inversion
and blocking parameters.