ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-338
D. Disturbance recorder function settings - Disturbance Rec
Summary of parameters:
Text Units Default Min. Max. Step
ParSet 4..1 P1 (Select)
StationNr 1 0 99 1
preEvent ms 40 40 400 20
Event ms 100 100 3000 50
postEvent ms 40 40 400 20
recMode A (Select)
TrigMode TrigOnStart (Select)
StorageMode StopOnFull (Select)
BinOutput SignalAddr ER
MemFullSign SignalAddr ER
AnalogInp 1 CT/VT-Addr
AnalogInp 2 CT/VT-Addr
.
.
AnalogInp 12 CT/VT-Addr
BinInp 1 BinaryAddr F
BinInp 2 BinaryAddr F
.
.
BinInp 16 BinaryAddr F
BinInp 1 no trig (Select)
BinInp 2 no trig (Select)
.
.
BinInp 16 no trig (Select)
MWAInp 1 MeasVar
.
.
MWAInp 12 MeasVar
MWAScale1 Factor 1 1 1000 1
.
.
MWAScale12 Factor