REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
5-33
The arrangement of the c.t. and v.t. input channels is established
by the ordering code (K...). Prior to assigning the c.t. and v.t. in-
put channels, the K code in the menu “Edit Relay Configuration”
must be set (see Section 3.4.1.).
Only the first phase of a three-phase group may be selected; the
other two phases are automatically included without any special
indication. Any channel may be selected, on the other hand, for
a single-phase function.
The channel number is indicated in the parameter value column
of the “Edit function parameters” window.
5.5.4.2. Signalling channels
Signals can be assigned individually to the event recorder, up to
two physical outputs (LED’s, signalling and tripping relays and
distributed outputs) and an output to a station control system
(SCS) and for interlocking purposes (ITL). The bleep sounds if
an attempt is made to use more than two physical outputs.
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛABB Switzerland LtdÛÛÛÛÛÛÛÛÛÛÛÛExampleÛÛÛÛÛÛÛÛÛÛÛÛÛREG316*4 Generator TerminalÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛÚEdit Function ParametersÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ¿Û
Û³ ³Û
Û³ Func Nr 2 - Voltage-DT * V> Max Voltage * ³Û
Û³ ³Û
Û³ ParSet4..1 ÉSelect Binary OutputÍ» Select ³Û
Û³ Trip º º ³Û
Û³ Delay º Signal LED's º s ³Û
Û³ V-Setting º Signal Relays º UN ³Û
Û³ MaxMin º Event Recording º Select ³Û
Û³ NrOfPhases º Trip Relays º ³Û
Û³ VoltageInp º Signal to SCS º AnalogAddr ³Û
Û³ BlockInp º Output to RBO's º BinaryAddr ³Û
Û³ Trip º Output to ITL º SignalAddr ³Û
Û³ Start º RETURN º SignalAddr ³Û
Û³ RETURN/ENTER º º ³Û
Û³ ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍͼ ³Û
Û³ ³Û
Û³ ³Û
ÛÀÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÙÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
ÛOn - Line 9600 bps SCS:SPAÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛV6.2b | V6.2bÛ
ÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛÛ
Fig. 5.8 Setting signalling channels
LED signals
Before LED’s can be assigned, the respective I/O unit (1 for
LED’s 1 to 8 or 2 for LED’S 9 to 16) must be selected in the
“Select I/O slot” window. The “LED’s” selection window then ap-
pears.