REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
5-41
Always TRUE or Always FALSE
The binary inputs of functions can be set permanently on (logical
1) or off (logical 0) by moving the selection bar to the corre-
sponding line and pressing <Enter>.
“T” (true) in the parameter value column of the “Edit function pa-
rameters” window indicates a permanently switched on input and
“F” (flase) a permanently switched off input.
System binary input
Every function input can be assigned either inverted or non-
inverted to a system binary input (opto-coupler input). The re-
spective I/O unit (1 to 4) is selected first and then the “Binary in-
put channels” selection window opens:
ÚSelect Binary InputÄÄÄ¿
³ ³
³ AlÚSelect IO-SlotÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ¿
³ Al³ ³
³ Bi³ > 1 ³
³ Ou³ ÉBinary Input ChannelsÍÍÍÍ»
³ In³ Usable IO-Slotº º
³ In³ ºÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄÚÄÄ¿º
³ In³ 1, 2 º³ 1³ 2³ 3³ 4³ 5³ 6³ 7³ 8³º
³ RE³ º³I ³ ³ ³ ³ ³ ³ ³ ³º
³ ÀÄÄÄÄÄÄÄÄÄÄÄÄÄÄĺÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÀÄÄÙº
ÀÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄĺCB open º
º º
ÈÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍÍͼ
Fig. 5.17 “Binary input channels” selection window
The fields representing the binary input channels in the selection
window are designated as follows:
Top: 1...14 : Channel No.
Bottom: X : selected channel (<Ins> key)
I : selected channel inverted (<-> key).
Any user comment is displayed in the lower part of the window
for the field currently selected.