REG 316*4 1MRB520049-Uen / Rev. C ABB Switzerland Ltd
6-5
The A/D converter 316EA62 or 316EA63 generates a number of
diagnostic messages:
Designation Function Weighting
RDY Device ready 0001H
Gr2Err Local value error 0020H
Gr3Err Error in the values received from the
transmitting device
0040H
Param Parameter error 0080H
Example
Event list after switching the device off and on:
MODURES - Events EXAMPLE
------------------------------------------------------------------------------
0 1998-03-30 11:37;08.338 Supply failure CPU 1
1 1998-03-30 11:37;08.338 System start
2 1998-03-30 11:37;08.338 Diagnosis: Main processor VC61 ready (0001H)
3 1998-03-30 11:37;08.338 Diagnosis: A/D processor EA6. not ready
4 1998-03-30 11:37;08.338 Diagnosis: Internal A/D ready (0001H)
5 1998-03-30 11:37;08.338 Diagnosis: System status: OK
6 1998-03-30 11:37;09.050 ParSatz2 ACTIVE
7 1998-03-30 11:37;09.056 Protection restart
8 1998-03-30 11:37;09.058 Relay ready ACTIVE
9 1998-03-30 11:37;09.058 Bin.I/P. No. 1/ 2 (Q0_OPEN ) ACTIVE
Bin.I/P. No. 1/ 4 (Q1_OPEN ) ACTIVE
Bin.I/P. No. 1/ 6 (Q2_OPEN ) ACTIVE
Bin.I/P. No. 1/ 8 (Q9_OPEN ) ACTIVE
Bin.I/P. No. 1/10 (Q8_OPEN ) ACTIVE
Bin.I/P. No. 1/12 (Q51_OPEN ) ACTIVE
Bin.I/P. No. 1/14 (Q52_OPEN ) ACTIVE
10 1998-03-30 11:37;09.058 Bin.I/P. No. 2/10 (BUS-TIE_OPEN ) ACTIVE
Bin.I/P. No. 2/12 (Q51_OPEN ) ACTIVE
Bin.I/P. No. 2/14 (Q52_OPEN ) ACTIVE
11 1998-03-30 11:37;40.051 MMC active ACTIVE.