EasyManua.ls Logo

ABB REG316 4 Series - Page 640

ABB REG316 4 Series
980 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Numerical generator protection REG316*4
1MRK502004-Ben
Page 12
Technical data Hard-
ware (cont’d)
Technical data Hard-
ware (cont’d)
ABB Switzerland Ltd
Utility Automation
Table 7: Auxiliary supply
Table 8: General data
Supply voltage
Voltage range 36 to 312 V DC
Voltage interruption bridging time >50 ms
Fuse rating ³4 A
Load on station battery at normal operation
(1 relay energized) <20 W
during a fault
(all relays energized)
with 1 I/O unit
with 2 I/O units
with 3 I/O units
with 4 I/O units
<22 W
<27 W
<32 W
<37 W
Additional load of the options
SPA, IEC 60870-5-103 or LON interface
MVB interface
1.5 W
2.5 W
Buffer time of the event list and fault recorder data at
loss of auxiliary supply
>2 days (typ. 1 month)
Temperature range
operation
storage
-10° C to +55° C
-40° C to +85° C
EN 60255-6 (1994),
IEC 60255-6 (1988)
Humidity 93%, 40° C, 4 days IEC 60068-2-3 (1969)
Seismic test 5 g, 30 s, 1 to 33 Hz
(1 octave/min)
IEC 60255-21-3 (1995),
IEEE 344 (1987)
Leakage resistance >100 MW, 500 V DC EN 60255-5 (2001),
IEC 60255-5 (2000)
Insulation test 2 kV, 50 Hz, 1 min
1 kV across open contacts
EN 60255-5 (2001),
IEC 60255-5 (2000),
EN 60950 (1995)
Surge voltage test 5 kV, 1.2/50 ms EN 60255-5 (2001),
IEC 60255-5 (2000) *
1 MHz burst disturbance test 1.0/2.5 kV, Cl. 3; 1MHz,
400 Hz rep.freq.
IEC 60255-22-1 (1988),
ANSI/IEEE C37.90.1
(1989)
Fast transient test 2/4 kV, Cl. 4 EN 61000-4-4 (1995),
IEC 61000-4-4 (1995)
Electrostatic discharge test
(ESD)
6/8 kV (10 shots), Cl. 3 EN 61000-4-2 (1996),
IEC 61000-4-2 (2001)
Immunity to magnetic interfer-
ence at power system frequen-
cies
300 A/m; 1000 A/m; 50/60 Hz
EN 61000-4-8 (1993),
IEC 61000-4-8 (1993)
Radio frequency interference test
(RFI)
• 0.15-80 MHz, 80% amplitude modulated
10 V, Cl. 3
• 80-1000 MHz, 80% amplitude modulated
10 V/m, Cl. 3
• 900 MHz, puls modulated
10 V/m, Cl. 3
EN 61000-4-6 (1996)
EN 61000-4-6 (1996),
EN 61000-4-3 (1996),
IEC 61000-4-3 (1996),
ENV 50204 (1995)
Emission Cl. A EN 61000-6-2 (2001),
EN 55011 (1998),
CISPR 11 (1990)
* Reduced values apply for repeat tests according to IEC publication 255-5, Clauses 6.6 and 8.6.