Numerical generator protection REG316*4
1MRK502004-Ben
Page 16
Technical Data Func-
tions (cont’d)
Technical Data Func-
tions (cont’d)
ABB Switzerland Ltd
Utility Automation
Table 15: Metering function UIfPQ
Memory duration 0.2 s to 60 s in steps of 0.01 s
Accuracy of pick-up setting (at f
N
)
Reset ratio
Accuracy of angle measurement
(at 0.94 to 1.06 f
N
)
Accuracy class of the operating time acc. to British
Standard 142
±5%
>94%
±5°
E 10
Voltage input range
Voltage memory range
Accuracy of angle measurement at voltage mem-
ory
Frequency dependence of angle measurement at
voltage memory
Max. Response time without delay
0.005 to 2 U
N
<0.005 U
N
±20°
±0.5°/Hz
60 ms
· Single-phase measurement of voltage, current, frequency, real power and apparent power
· Choice of measuring phase-to-ground or phase-to phase voltages
· Suppression of DC components and harmonics in current and voltage
· Compensation of phase errors in main and input c.t’s and v.t’s
Settings:
Phase-angle -180° to +180° in steps of 0.1°
Reference value of the power S
N
0.2 to 2.5 S
N
in steps of 0.001 S
N
Refer to Table 46 for accuracy.
Table 16: Three-phase measuring module
· Three-phase measurement of voltage (star or delta), current, frequency, real and apparent power and
power factor.
· Two independent impulse counter inputs for calculation of interval and accumulated energy. The three-
phase measurement and the impulse counters can be used independently and may also be disabled.
· This function may be configured four times.
Settings:
Angle -180° to +180° in steps of 0.1°
Reference value for power 0.2 to 2.5 S
N
in steps of 0.001 S
N
t1-Interval 1 min., 2 min., 5 min., 10 min., 15 min., 20 min.,
30 min., 60 min. or 120 min.
Scale factor of power 0.0001 to 1
Max. impulse frequency 25 Hz
Min. impulse duration
Accuracy of time interval
10 ms
±100 ms
See Table 46 for accuracy