ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. F
3-30
HighSetInp
determines whether the normal or high-set basic setting g is
used.
F: - not used
xx: - all binary inputs (or outputs of protection func-
tions).
Trip
Output for the signalling tripping.
Trip-R
Output for signalling tripping by R phase.
Trip-S
Output for signalling tripping by S phase.
Trip-T
Output for signalling tripping by T phase.
Inrush
Output for signalling inrush current.
Stabilizing
Output for signalling I
H
> b during through-faults.
Note:
The differential protection function does not have a pick-up sig-
nal. Every time it trips, the signal ‘GenStart’ is set together with
‘Trip’, providing the tripping command is configured to be
recorded as an event (ER).