REG 316*4 1MRB520049-Uen / Rev. E ABB Switzerland Ltd
9-37
9.6.27. OLoad-Stator 14
Basic channel No.: 14
Summary of parameters:
Address Access Text Unit Default Min. Max. Step
14S4 R ParSet4..1 <Select> P1 00000010B 00011110B
14S5 R TRIP 00000000B
14S9 R k1-Setting s 041.4 1.0 120.0 0.1
14S10 R I-Start IB 1.10 1.00 1.60 0.01
14S11 R t-min s 0010.0 1.0 120.0 0.1
14S12 R tg s 0120.0 10.0 2000.0 10.0
14S13 R t-max s 0300.0 100.0 2000.0 10.0
14S14 R t-Reset s 0120.0 10.0 2000.0 10.0
14S15 R IB-Setting IN 1.00 0.50 2.50 0.01
14S16 R NrOfPhases 3 1 3 2
Measured variables
Address Access Text Dec.
14V1 R IN 3
Tripping levels
Address Access Text Dec.
14Q1 R IN 3
Event list
Event No. Cause Event mask Enable code Status
14E1 Trip Set V155 1 14I1
14E2 Ditto Reset V155 2
14E3 Start Set V155 4 14I2
14E4 Ditto Reset V155 8