ABB Switzerland Ltd REG 316*4 1MRB520049-Uen / Rev. E
9-46
Address Access Text Unit Default Min. Max. Step
15S1 R SOFT <Select> off 0 2 1
off 0
Non-dir 1
Fwards OR2 2
15S2 R
EventRecFull
<Select> off 0 1 1
off 0
on 1
15S3 R 3U0min UN 000.00 0 2 0.01
15S4 R U Weak UN 000.00 0 2 0.01
15S5 R I OC BU IN 000.00 0 10 0.01
15S6 R Del OC BU s 005.00 0 10 0.01
15S7 R
GndFaultMode
<Select> I0 0 3 1
I0 0
I0 OR U0 1
I0 AND U0 2
Blocked 3
15S9 R Dir Def <Select> Non-dir 1 2 1
Non-dir 1
Fwards 2
15S10 R TripMode <Select> 1PhTrip 1 3 1
1PhTrip 1
3PhTrip 2
3PhTripDel3 3
15S11 R SOFT10sec <Select> off 0 1 1
off 0
on 1
15S12 R t1EvolFaults s 003.00 0 10 0.01
15S13 R ZExtension <Select> off 0 1 1
off 0
on 1
15S14 R Weak <Select> off 0 1 1
off 0
on 1

Table of Contents