Table 16. Environmental conditions
Description Value
Operating temperature range -25...+55ºC (continuous)
Short-time service temperature range -40...+70ºC (<16h)
Note: Degradation in MTBF and HMI performance outside the
temperature range of -25...+55ºC
Relative humidity <93%, non-condensing
Atmospheric pressure 86...106 kPa
Altitude up to 2000 m
Transport and storage temperature range -40...+85ºC
Table 17. Environmental tests
Description
Type test value Reference
Cold tests operation
storage
96 h at -25ºC
16 h at -40ºC
96 h at -40ºC
IEC 60068-2-1/ANSI C37.90-2005 (chapter 4)
Dry heat tests operation
storage
16 h at +70ºC
96 h at +85ºC
IEC 60068-2-2/ANSI C37.90-2005 (chapter 4)
Damp heat tests steady state
cyclic
240 h at +40ºC
humidity 93%
6 cycles at +25 to +55ºC
humidity 93...95%
IEC 60068-2-78
IEC 60068-2-30
Generator protection REG650
1MRK 502 050-BEN B
Product version: 1.3