138.227.102.10 with subnet mask 255.255.255.0 and port 2 has IP-
address 138.227.103.10 with subnet mask 255.255.255.0
18.3.2 Settings
Table 722: IEC61850-8-1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
PortSelGOOSE Front
LANAB
LANCD
-
- LANAB Port selection for GOOSE communication
PortSelMMS Front
LANAB
LANCD
Any
-
- Any Port selection for MMS communication
ProtocolEdition Ed 1
Ed 2
- - Ed 1 Protocol Edition
RemoteModControl Off
Maintenance
All levels
-
- Off Remote Mode Control
AllowGOOSESimulation No
Yes
- - No Allow enabling of GOOSE Simulation
IEC61850BufTimEnable Disabled
Enabled
- - Enabled Enable BRC buf time behavior
18.3.3 Technical data
Table 723: Communication protocols
Function
Value
Protocol IEC 61850-8-1
Communication speed for the IEDs 100BASE-FX
Protocol IEC 60870–5–103
Communication speed for the IEDs 9600 or 19200 Bd
Protocol DNP3.0
Communication speed for the IEDs 300–19200 Bd
Protocol TCP/IP, Ethernet
Communication speed for the IEDs 100 Mbit/s
18.3.4 Generic communication function for Single Point indication
SPGAPC, SP16GAPC
Section 18 1MRK502052-UEN B
Station communication
994
Technical manual