EasyManua.ls Logo

ABB REG670 - Signals

ABB REG670
1298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18.3.5.3 Signals
Table 728: MVGAPC Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of function
IN REAL 0 Analog input value
Table 729: MVGAPC Output signals
Name Type Description
VALUE REAL Magnitude of deadband value
RANGE INTEGER Range
18.3.5.4 Settings
Table 730: MVGAPC Non group settings (basic)
Name Values (Range) Unit Step Default Description
BasePrefix micro
milli
unit
kilo
Mega
Giga
Tera
-
- unit Base prefix (multiplication factor)
MV db 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
MV zeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of range
MV hhLim -5000.00 - 5000.00 xBase 0.01 900.00 High High limit multiplied with the base
prefix (multiplication factor)
MV hLim -5000.00 - 5000.00 xBase 0.01 800.00 High limit multiplied with the base prefix
(multiplication factor)
MV lLim -5000.00 - 5000.00 xBase 0.01 -800.00 Low limit multiplied with the base prefix
(multiplication factor)
MV llLim -5000.00 - 5000.00 xBase 0.01 -900.00 Low Low limit multiplied with the base
prefix (multiplication factor)
MV min -5000.00 - 5000.00 xBase 0.01 -1000.00 Minimum value multiplied with the base
prefix (multiplication factor)
MV max -5000.00 - 5000.00 xBase 0.01 1000.00 Maximum value multiplied with the base
prefix (multiplication factor)
MV dbType Cyclic
Dead band
Int deadband
-
- Dead band Reporting type
MV limHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
Section 18 1MRK502052-UEN B
Station communication
998
Technical manual

Table of Contents

Other manuals for ABB REG670