18.3.5.3 Signals
Table 728: MVGAPC Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of function
IN REAL 0 Analog input value
Table 729: MVGAPC Output signals
Name Type Description
VALUE REAL Magnitude of deadband value
RANGE INTEGER Range
18.3.5.4 Settings
Table 730: MVGAPC Non group settings (basic)
Name Values (Range) Unit Step Default Description
BasePrefix micro
milli
unit
kilo
Mega
Giga
Tera
-
- unit Base prefix (multiplication factor)
MV db 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
MV zeroDb 0 - 100000 m% 1 500 Zero point clamping in 0,001% of range
MV hhLim -5000.00 - 5000.00 xBase 0.01 900.00 High High limit multiplied with the base
prefix (multiplication factor)
MV hLim -5000.00 - 5000.00 xBase 0.01 800.00 High limit multiplied with the base prefix
(multiplication factor)
MV lLim -5000.00 - 5000.00 xBase 0.01 -800.00 Low limit multiplied with the base prefix
(multiplication factor)
MV llLim -5000.00 - 5000.00 xBase 0.01 -900.00 Low Low limit multiplied with the base
prefix (multiplication factor)
MV min -5000.00 - 5000.00 xBase 0.01 -1000.00 Minimum value multiplied with the base
prefix (multiplication factor)
MV max -5000.00 - 5000.00 xBase 0.01 1000.00 Maximum value multiplied with the base
prefix (multiplication factor)
MV dbType Cyclic
Dead band
Int deadband
-
- Dead band Reporting type
MV limHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common
for all limits)
Section 18 1MRK502052-UEN B
Station communication
998
Technical manual