Name Values (Range) Unit Step Default Description
TypNo7 Absolute
Relative
- - Absolute Type identification (TYP)
TypNo8 Absolute
Relative
- - Absolute Type identification (TYP)
GiNo1 Excluded
Included
- - Included Response and status change (GI)
GiNo2 Excluded
Included
- - Included Response and status change (GI)
GiNo3 Excluded
Included
- - Included Response and status change (GI)
GiNo4 Excluded
Included
- - Included Response and status change (GI)
GiNo5 Excluded
Included
- - Included Response and status change (GI)
GiNo6 Excluded
Included
- - Included Response and status change (GI)
GiNo7 Excluded
Included
- - Included Response and status change (GI)
GiNo8 Excluded
Included
- - Included Response and status change (GI)
The FunctionType parameter associates a particular instance of the function block
with a FUN. Refer to the IEC 60870-5-103 standard for details.
The InfNon parameters are used to associate each individual input signal with a
userdefined INF. Refer to the IEC 60870-5-103 standard for details.
The TypNon parameters determine if messages use absolute or relative time. This
adheres to the TYPE IDENTIFICATION (TYP) message types 1 (time-tagged
message) and 2 (time-tagged message with relative time) of the IEC 60870-5-103
standard.
The GiNon parameters determine whether a message is sent as a part of a GI reply or
not. Refer to the IEC 60870-5-103 standard for details.
18.6.10 Function commands for IEC 60870-5-103 I103CMD
18.6.10.1 Functionality
I103CMD is a command function block in control direction with pre-defined output
signals. The signals are in steady state, not pulsed, and stored in the IED in case of
restart.
1MRK502052-UEN B Section 18
Station communication
1043
Technical manual