18.6.11.2 Identification
Function description Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
IED commands for IEC 60870-5-103 I103IEDCMD - -
18.6.11.3 Function block
IEC10000283-1-en.vsd
I103IEDCMD
BLOCK 19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
IEC10000283 V1 EN
Figure 480: I103IEDCMD function block
18.6.11.4 Signals
Table 766: I103IEDCMD Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of commands
Table 767: I103IEDCMD Output signals
Name
Type Description
19-LEDRS BOOLEAN Information number 19, reset LEDs
23-GRP1 BOOLEAN Information number 23, activate setting group 1
24-GRP2 BOOLEAN Information number 24, activate setting group 2
25-GRP3 BOOLEAN Information number 25, activate setting group 3
26-GRP4 BOOLEAN Information number 26, activate setting group 4
18.6.11.5 Settings
Table 768: I103IEDCMD Non group settings (basic)
Name
Values (Range) Unit Step Default Description
FunctionType 1 - 255 - 1 255 Function type (1-255)
1MRK502052-UEN B Section 18
Station communication
1045