INF Description GI TYP COT
6* Input signal 06 x/- 1/2 1,7,(9)
7* Input signal 07 x/- 1/2 1,7,(9)
8* Input signal 08 x/- 1/2 1,7,(9)
1) * User defined information number
Supervision indications in monitor direction, I103SUPERV
Indication block for supervision in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for output signals.
Table 782: I103SUPERV supported functions
INF Description TYP GI COT
32 Measurand supervision I 1 Y 1,7,9
33 Measurand supervision U 1 Y 1,7,9
37 I>>back-up operation 1 Y 1,7,9
38 VT fuse failure 1 Y 1,7,9
46 Group warning 1 Y 1,7,9
47 Group alarm 1 Y 1,7,9
Earth fault indications in monitor direction, I103EF
Indication block for earth fault in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter FunctionType.
Information number is defined for each output signal.
Table 783: I103EF supported indications
INF
Description
51 Earth fault forward
52 Earth fault reverse
Fault indications in monitor direction, type 1, I103FltDis
Fault indication block for faults in monitor direction with defined functions.
The instance type is suitable for distance protection function.
FUNCTION TYPE parameter for each block.
1MRK502052-UEN B Section 18
Station communication
1053
Technical manual