INFORMATION NUMBER is defined for each input signal.
Number of instances: 1
Info. no.
Message Supported
64 Start L1 Yes
65 Start L2 Yes
66 Start L3 Yes
67 Start IN Yes
84 General start Yes
69 Trip L1 Yes
70 Trip L2 Yes
71 Trip L3 Yes
68 General trip Yes
74 Fault forward/line Yes
75 Fault reverse/busbar Yes
78 Zone 1 Yes
79 Zone 2 Yes
80 Zone 3 Yes
81 Zone 4 Yes
82 Zone 5 Yes
76 Signal transmitted Yes
77 Signal received Yes
73 SCL, Fault location in ohm Yes
Fault indications in monitor direction, type 2, I103FltStd
Fault indication block for faults in monitor direction with defined functions.
The instance type is suitable for line differential, transformer differential, overcurrent
and earth fault protection functions.
FUNCTION TYPE setting for each block.
INFORMATION NUMBER is defined for each input signal.
Number of instances: 1
Info. no.
Message Supported
64 Start L1 Yes
65 Start L2 Yes
66 Start L3 Yes
67 Start IN Yes
84 General start Yes
69 Trip L1 Yes
Table continues on next page
Section 18 1MRK502052-UEN B
Station communication
1054
Technical manual