EasyManua.ls Logo

ABB REG670 - Supervision of Analog Inputs

ABB REG670
1298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Card Name of signal Description Displayed on
local HMI as
Reasons for activation
ADM ADM-Error A/D
Module
Error
status
ADM32
Activated if the module has a hardware
error.
OEM OEM-Error Optical
Ethernet
Module
Error
status
OEM3nn
Activated if the module has a hardware
error.
n = slot number
LDCM
LDCM-Error Line
Differentia
l
Communi
cation
Module
Error
status
LDCM3nn Activated if the module has a hardware
error.
n = slot number
TRM
TRM-Error Transform
er Module
Error
status
TRM40
TRM TRM-Error Transform
er Module
Error
status
TRM41
20.5.5.2 Supervision of analog inputs
The analog signals to the A/D converter is internally distributed into two different
converters, one with low amplification and one with high amplification.
When the signal is within measurable limits on both channels, a direct comparison of
the two A/D converter channels can be performed. If the validation fails, the CPU will
be informed and an alarm will be given for A/D converter failure.
20.5.6 Technical data
Table 835: Self supervision with internal event list
Data
Value
Recording manner Continuous, event controlled
List size 40 events, first in-first out
Section 20 1MRK502052-UEN B
Basic IED functions
1102
Technical manual

Table of Contents

Other manuals for ABB REG670

Related product manuals