Table 863: SMAI1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
DFTRefExtOut InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
- - InternalDFTRef DFT reference for external output
DFTReference InternalDFTRef
DFTRefGrp1
DFTRefGrp2
DFTRefGrp3
DFTRefGrp4
DFTRefGrp5
DFTRefGrp6
DFTRefGrp7
DFTRefGrp8
DFTRefGrp9
DFTRefGrp10
DFTRefGrp11
DFTRefGrp12
External DFT ref
- - InternalDFTRef DFT reference
ConnectionType Ph-N
Ph-Ph
- - Ph-N Input connection type
AnalogInputType Voltage
Current
- - Voltage Analog input signal type
Table 864: SMAI1 Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
Negation Off
NegateN
Negate3Ph
Negate3Ph+N
-
- Off Negation
MinValFreqMeas 5 - 200 % 1 10 Limit for frequency calculation in % of
UBase
1MRK502052-UEN B Section 20
Basic IED functions
1131
Technical manual