EasyManua.ls Logo

ABB REG670 - Technical Data

ABB REG670
1298 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21.2.9.6 Technical data
Table 904: SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Function of quantity
Static binary output trip
Rated voltage 48-60 VDC 110-250 VDC
Number of outputs 6 6
Impedance open state ~300 kΩ ~810 kΩ
Test voltage across open contact, 1
min
No galvanic separation No galvanic separation
Current carrying capacity:
Continuous 5 A 5 A
1.0 s 10 A 10 A
Making capacity at capacitive load
with the maximum capacitance of
0.2 μF :
0.2 s 30 A 30 A
1.0 s 10 A 10 A
Breaking capacity for DC with L/R
40 ms
48 V/1 A 110 V/0.4 A
60 V/0.75 A 125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Operating time < 1 ms < 1 ms
Table 905: SOM - Static Output module data (reference standard: IEC 61810-2):
Electromechanical relay outputs
Function of quantity
Trip and signal relays
Max system voltage 250 V AC/DC
Number of outputs 6
Test voltage across open contact, 1 min 1000 V rms
Current carrying capacity:
Continuous 8 A
1.0 s 10 A
Making capacity at capacitive load with the
maximum capacitance of 0.2 μF:
0.2 s 30 A
1.0 s 10 A
Breaking capacity for DC with L/R ≤ 40 ms 48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
1MRK502052-UEN B Section 21
IED hardware
1173
Technical manual

Table of Contents