Name Type Description
CH4 REAL Analog input 4
CH5 REAL Analog input 5
CH6 REAL Analog input 6
21.2.11.4 Settings
Table 915: MIM Non group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off/On
MaxReportT 0 - 3600 s 1 1 Maximum time between reports
EnDeadBandCh1 Off
On
- - Off Enable amplitude deadband reporting for
channel 1
DeadBandCh1 0.00 - 20.00 mA 0.01 1.00 Deadband amplitude for channel 1
IMinCh1 -25.00 - 25.00 mA 0.01 4.00 Min current of transducer for Channel 1
IMaxCh1 -25.00 - 25.00 mA 0.01 20.00 Max current of transducer for Channel 1
ValueMinCh1 -10000000000.000
- 10000000000.000
- 0.001 4.000 Min primary value corr. to IMinCh1
ValueMaxCh1 -10000000000.000
- 10000000000.000
- 0.001 20.000 Max primary value corr. to IMaxCh1
EnDeadBandCh2 Off
On
- - Off Enable amplitude deadband reporting for
channel 2
DeadBandCh2 0.00 - 20.00 mA 0.01 1.00 Deadband amplitude for channel 2
IMinCh2 -25.00 - 25.00 mA 0.01 4.00 Min current of transducer for Channel 2
IMaxCh2 -25.00 - 25.00 mA 0.01 20.00 Max current of transducer for Channel 2
ValueMinCh2 -10000000000.000
- 10000000000.000
- 0.001 4.000 Min primary value corr. to IMinCh2
ValueMaxCh2 -10000000000.000
- 10000000000.000
- 0.001 20.000 Max primary value corr. to IMaxCh2
EnDeadBandCh3 Off
On
- - Off Enable amplitude deadband reporting for
channel 3
DeadBandCh3 0.00 - 20.00 mA 0.01 1.00 Deadband amplitude for channel 3
IMinCh3 -25.00 - 25.00 mA 0.01 4.00 Min current of transducer for Channel 3
IMaxCh3 -25.00 - 25.00 mA 0.01 20.00 Max current of transducer for Channel 3
ValueMinCh3 -10000000000.000
- 10000000000.000
- 0.001 4.000 Min primary value corr. to IMinCh3
ValueMaxCh3 -10000000000.000
- 10000000000.000
- 0.001 20.000 Max primary value corr. to IMaxCh3
EnDeadBandCh4 Off
On
- - Off Enable amplitude deadband reporting for
channel 4
DeadBandCh4 0.00 - 20.00 mA 0.01 1.00 Deadband amplitude for channel 4
IMinCh4 -25.00 - 25.00 mA 0.01 4.00 Min current of transducer for Channel 4
IMaxCh4 -25.00 - 25.00 mA 0.01 20.00 Max current of transducer for Channel 4