Table 953: Insulation tests, REX060, REX062 and REG670
Test Type test values Reference standard
Dielectric test 2.0 kV AC, 1 min IEC 60255-27
Impulse voltage test 5.0 kV, 1.2/50 µs, 0.5 J IEC 60255-27
Insulation resistance >100 MΩ at 500V DC IEC 60255-27
Table 954: Insulation tests, REX061
Test Type test values Reference standard
Dielectric test 7.48 kV DC, 1min
(connections to rotor)
2.8 kV DC, 1 min
IEEE 421.3
IEC 60255-27
Impulse voltage test
12.0 kV, 1.2/50 µs, 0.5 J
(connections to rotor)
5.0 kV, 1.2/50 µs, 0.5 J
IEC 60664-1
IEC 60255-27
Insulation resistance
>100 MΩ at 500V DC IEC 60255-27
Table 955: Mechanical tests
Test
Reference standards Requirements
Vibration response test IEC 60255-21-1 Class 2
Vibration endurance test
REG670 and REX060
REX061 and REX062
IEC 60255-21-1
Class 1
Class 2
Shock response test
REG670 and REX060
REX061 and REX062
IEC 60255-21-2
Class 1
Class 2
Shock withstand test
REG670 and REX060
REX061 and REX062
IEC 60255-21-2
Class 1
Class 2
Bump test
REG670 and REX060
REX061 and REX062
IEC 60255-21-2
Class 1
Class 2
Seismic test
REG670 and REX060
REX061 and REX062
IEC 60255-21-3
Class 2
Class 2 extended
1MRK502052-UEN B Section 22
Injection equipment hardware
1235