Figure 155: Under voltage seal-in for zone 2 and zone 3
7.10.8 Technical data
Table 150: ZGVPDIS Technical data
Function
Range or value Accuracy
Number of zones 3 -
Forward reach
(3.0 - 200.0)% of Z
r
where Z
r
=UBase/√3∗IBase
±5.0% of set impedance
Conditions:
Voltage range: (0.1 - 1.1) x U
r
Current range: (0.5 - 30) x I
r
Reverse reach
(3.0 - 200.0)% of Z
r
where Z
r
=UBase/√3∗IBase
±5.0% of set impedance
Conditions:
Voltage range: (0.1 - 1.1) x U
r
Current range: (0.5 - 30) x I
r
Impedance angle
(5 - 90) degrees -
Reset ratio 105% typically -
Start time at 1.2 to 0.8 x set
impedance
Min. = 15 ms
-
Max. = 35 ms
Independent time delay to
operate at 1.2 to 0.8 x set
impedance
(0.000 – 60.000) s
±0.2% or ±40 ms whichever is
greater