8.2.7 Operation principle
The Four step phase overcurrent protection OC4PTOC is divided into four different
sub-functions, one for each step. For each step x , where x is step 1, 2, 3 and 4, an
operation mode is set by DirModex: Off/Non-directional/Forward/Reverse.
The protection design can be divided in four parts:
The direction element
The harmonic Restraint Blocking function
The four step over current function
The mode selection
If VT inputs are not available or not connected, setting parameter
DirModex shall be left to default value, Non-directional.
en05000740-2-en.vsd
Direction
Element
4 step over current
element
One element for each
step
Harmonic
Restraint
Mode Selection
dirPh1Flt
dirPh2Flt
dirPh3Flt
harmRestrBlock
enableDir
enableStep1-4
DirectionalMode1-4
faultState
Element
faultState
I3P
U3P
START
TRIP
IEC05000740 V2 EN
Figure 158: Functional overview of OC4PTOC
1MRK502052-UEN B Section 8
Current protection
345
Technical manual