Name Values (Range) Unit Step Default Description
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 30% of Ir
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 100% of Ir
UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 5% of Ur
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 30% of Ur
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 100% of Ur
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 100% of Ir
Table 217: GUPPDUP Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Mode L1, L2, L3
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
- - Pos Seq Selection of measured current and
voltage
8.10.6 Monitored data
Table 218: GUPPDUP Monitored data
Name
Type Values (Range) Unit Description
P REAL - MW Active Power in MW
PPERCENT REAL - % Active power in % of
SBase
Q REAL - MVAr Reactive power in MVAr
QPERCENT REAL - % Reactive power in % of
SBase
8.10.7 Operation principle
A simplified scheme showing the principle of the power protection function is shown
in figure
195. The function has two stages with individual settings.
Section 8 1MRK502052-UEN B
Current protection
422