Table 222: GOPPDOP Output signals
Name Type Description
TRIP BOOLEAN Common trip signal
TRIP1 BOOLEAN Trip of stage 1
TRIP2 BOOLEAN Trip of stage 2
START BOOLEAN Common start
START1 BOOLEAN Start of stage 1
START2 BOOLEAN Start of stage 2
P REAL Active power P in MW
PPERCENT REAL Active power P in % of SBase
Q REAL Reactive power Q in MVAr
QPERCENT REAL Reactive power Q in % of SBase
8.11.5 Settings
Table 223: GOPPDOP Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off / On
OpMode1 Off
OverPower
- - OverPower Operation mode for stage 1 Off / On
Power1 0.0 - 500.0 %SB 0.1 120.0 Stage 1 overpower setting in Angle1
direction in % of SBase
Angle1 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for max power
senistivity stage 1
TripDelay1 0.01 - 6000.00 s 0.01 1.00 Trip delay for stage 1
DropDelay1 0.01 - 6000.00 s 0.01 0.06 Drop-off delay for stage 1
OpMode2 Off
OverPower
- - OverPower Operation mode for stage 2 Off / On
Power2 0.0 - 500.0 %SB 0.1 120.0 Stage 2 overpower setting in Angle2
direction in % of SBase
Angle2 -180.0 - 180.0 Deg 0.1 0.0 Characteristic angle for max power
senistivity stage 2
TripDelay2 0.01 - 6000.00 s 0.01 1.00 Trip delay for stage 2
DropDelay2 0.01 - 6000.00 s 0.01 0.06 Drop-off delay for stage 2