Table 224: GOPPDOP Group settings (advanced)
Name Values (Range) Unit Step Default Description
k 0.000 - 0.999 - 0.001 0.000 Low pass filter coefficient for power
measurement, P and Q
Hysteresis1 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 1 in % of
SBase
Hysteresis2 0.2 - 5.0 %SB 0.1 0.5 Absolute hysteresis of stage 2 in % of
SBase
IAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 5% of Ir
IAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 30% of Ir
IAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
current error at 100% of Ir
UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 5% of Ur
UAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 30% of Ur
UAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude correction compensates
voltage error at 100% of Ur
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 5% of Ir
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 30% of Ir
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Corr of error betw current and voltage
angles at 100% of Ir
Table 225: GOPPDOP Non group settings (basic)
Name
Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Mode L1, L2, L3
Arone
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3
- - Pos Seq Selection of measured current and
voltage
Section 8 1MRK502052-UEN B
Current protection
430
Technical manual