Name Values (Range) Unit Step Default Description
ResCrvType_UV2 Instantaneous
Frozen timer
Linearly decreased
-
- Instantaneous Selection of reset curve type for UV2
tResetDef_UV2 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for definite time
use of UV2
tResetIDMT_UV2 0.00 - 6000.00 s 0.01 0.00 Reset time delay in sec for IDMT curves
for UV2
A_UV2 0.005 - 999.000 - 0.001 0.140 Parameter A for customer programmable
curve for UV2
B_UV2 0.500 - 99.000 - 0.001 1.000 Parameter B for customer programmable
curve for UV2
C_UV2 0.000 - 1.000 - 0.001 1.000 Parameter C for customer programmable
curve for UV2
D_UV2 0.000 - 10.000 - 0.001 0.000 Parameter D for customer programmable
curve for UV2
P_UV2 0.001 - 10.000 - 0.001 0.020 Parameter P for customer programmable
curve for UV2
Table 330: CVGAPC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
11.1.6 Monitored data
Table 331: CVGAPC Monitored data
Name
Type Values (Range) Unit Description
DIROC1 INTEGER 1=Forward
0=Non-
directional
2=Reverse
-
Directional mode of OC1
(nondir, forward,reverse)
DIROC2 INTEGER 1=Forward
0=Non-
directional
2=Reverse
-
Directional mode of OC2
(nondir, forward,reverse)
CURRENT REAL - A Measured current value
ICOSFI REAL - A Measured current
multiplied with cos (Phi)
VOLTAGE REAL - kV Measured voltage value
UIANGLE REAL - deg Angle between voltage
and current
1MRK502052-UEN B Section 11
Multipurpose protection
575