13.3.5 Settings
Table 357: VDSPVC Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Mode Off / On
Ud>MainBlock 10.0 - 80.0 %UB 0.1 20.0 Blocking picked up voltage level in % of
UBase when main fuse fails
Ud>PilotAlarm 10.0 - 80.0 %UB 0.1 30.0 Alarm picked up voltage level in % of
UBase when pilot fuse fails
SealIn Off
On
- - On Seal in functionality Off/On
USealIn 0.0 - 100.0 %UB 0.1 70.0 Operate level of seal-in voltage in % of
UBase
Table 358: VDSPVC Non group settings (basic)
Name Values (Range) Unit Step Default Description
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
Table 359: VDSPVC Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
ConTypeMain Ph-N
Ph-Ph
- - Ph-N Selection of connection type for main fuse
group
ConTypePilot Ph-N
Ph-Ph
- - Ph-N Selection of connection type for pilot fuse
group
13.3.6 Monitored data
Table 360: VDSPVC Monitored data
Name
Type Values (Range) Unit Description
UL1DIF_A REAL - kV Differential voltage phase
L1 for alarm functionality
UL2DIF_A REAL - kV Differential voltage phase
L2 for alarm functionality
UL3DIF_A REAL - kV Differential voltage phase
L3 for alarm functionality
UL1DIF_B REAL - kV Differential voltage phase
L1 for block functionality
UL2DIF_B REAL - kV Differential voltage phase
L2 for block functionality
UL3DIF_B REAL - kV Differential voltage phase
L3 for block functionality
1MRK502052-UEN B Section 13
Secondary system supervision
621