Name Values (Range) Unit Step Default Description
ULowBusEnerg 10.0 - 80.0 %UBB 1.0 40.0 Voltage low limit bus for energizing check
in % of UBaseBus
ULowLineEnerg 10.0 - 80.0 %UBL 1.0 40.0 Voltage low limit line for energizing check
in % of UBaseLine
UMaxEnerg 50.0 - 180.0 %UB 1.0 115.0 Maximum voltage for energizing in % of
UBase, Line and/or Bus
tAutoEnerg 0.000 - 60.000 s 0.001 0.100 Time delay for automatic energizing
check
tManEnerg 0.000 - 60.000 s 0.001 0.100 Time delay for manual energizing check
Table 365: SESRSYN Non group settings (basic)
Name Values (Range) Unit Step Default Description
SelPhaseBus1 Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
- Phase L1 Select phase for busbar1
GblBaseSelBus 1 - 12 - 1 1 Selection of one of the Global Base Value
groups, Bus
GblBaseSelLine 1 - 12 - 1 1 Selection of one of the Global Base Value
groups, Line
SelPhaseBus2 Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
- Phase L1 Select phase for busbar2
SelPhaseLine1 Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
- Phase L1 Select phase for line1
SelPhaseLine2 Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
-
- Phase L1 Select phase for line2
CBConfig No voltage sel.
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB
-
- No voltage sel. Select CB configuration
Section 14 1MRK502052-UEN B
Control
630
Technical manual