14.2.9.5 Signals
Table 385: DB_BUS_A Input signals
Name
Type Default Description
QA1_OP BOOLEAN 0 QA1 is in open position
QA1_CL BOOLEAN 0 QA1 is in closed position
QB1_OP BOOLEAN 0 QB1 is in open position
QB1_CL BOOLEAN 0 QB1 is in closed position
QB61_OP BOOLEAN 0 QB61 is in open position
QB61_CL BOOLEAN 0 QB61 is in closed position
QC1_OP BOOLEAN 0 QC1 is in open position
QC1_CL BOOLEAN 0 QC1 is in closed position
QC2_OP BOOLEAN 0 QC2 is in open position
QC2_CL BOOLEAN 0 QC2 is in closed position
QC3_OP BOOLEAN 0 QC3 is in open position
QC3_CL BOOLEAN 0 QC3 is in closed position
QC11_OP BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in open
position
QC11_CL BOOLEAN 0 Earthing switch QC11 on busbar WA1 is in closed
position
EXDU_ES BOOLEAN 0 No transm error from bay containing earthing
switch QC11
QB61_EX1 BOOLEAN 0 External condition for apparatus QB61
QB61_EX2 BOOLEAN 0 External condition for apparatus QB61
QB1_EX1 BOOLEAN 0 External condition for apparatus QB1
QB1_EX2 BOOLEAN 0 External condition for apparatus QB1
Table 386: DB_BUS_A Output signals
Name
Type Description
QA1CLREL BOOLEAN Closing of QA1 is allowed
QA1CLITL BOOLEAN Closing of QA1 is forbidden
QB61REL BOOLEAN Switching of QB61 is allowed
QB61ITL BOOLEAN Switching of QB61 is forbidden
QB1REL BOOLEAN Switching of QB1 is allowed
QB1ITL BOOLEAN Switching of QB1 is forbidden
QC1REL BOOLEAN Switching of QC1 is allowed
QC1ITL BOOLEAN Switching of QC1 is forbidden
QC2REL BOOLEAN Switching of QC2 is allowed
QC2ITL BOOLEAN Switching of QC2 is forbidden
QB1OPTR BOOLEAN QB1 is in open position
QB1CLTR BOOLEAN QB1 is in closed position
VPQB1TR BOOLEAN Switch status of QB1 is valid (open or closed)