Table 423: RESIN2 Output signals
Name Type Description
ACK_F_B BOOLEAN All other bays have acknow. the reserv. req. from
this bay
ANY_ACK BOOLEAN Any other bay has acknow. the reserv. req. from
this bay
VALID_TX BOOLEAN The reserv. and acknow. signals from other bays
are valid
RE_RQ_B BOOLEAN Request from other bay to reserve this bay
V_RE_RQ BOOLEAN Check if the request of reserving this bay is valid
EXCH_OUT INTEGER Used for exchange signals between different ResIn
blocks
14.3.10.4 Settings
Table 424: RESIN1 Non group settings (basic)
Name Values (Range) Unit Step Default Description
FutureUse Bay in use
Bay future use
- - Bay in use The bay for this ResIn block is for future
use
Table 425: RESIN2 Non group settings (basic)
Name
Values (Range) Unit Step Default Description
FutureUse Bay in use
Bay future use
- - Bay in use The bay for this ResIn block is for future
use
14.3.10.5 Operation principle
The reservation input (RESIN) function is based purely on Boolean logic conditions.
The logic diagram in Figure 354 shows how the output signals are created. The inputs
of the function block are connected to a receive function block representing signals
transferred over the station bus from another bay.
1MRK502052-UEN B Section 14
Control
741
Technical manual