Name Values (Range) Unit Step Default Description
CTStarPoint7 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec7 1 - 10 A 1 1 Rated CT secondary current
CTprim7 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint8 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec8 1 - 10 A 1 1 Rated CT secondary current
CTprim8 1 - 99999 A 1 3000 Rated CT primary current
CTStarPoint9 FromObject
ToObject
- - ToObject ToObject= towards protected object,
FromObject= the opposite
CTsec9 1 - 10 A 1 1 Rated CT secondary current
CTprim9 1 - 99999 A 1 3000 Rated CT primary current
VTsec10 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim10 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec11 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim11 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
VTsec12 0.001 - 999.999 V 0.001 110.000 Rated VT secondary voltage
VTprim12 0.05 - 2000.00 kV 0.05 400.00 Rated VT primary voltage
3.5 Monitored data
Table 14: AISVBAS Monitored data
Name
Type Values (Range) Unit Description
Status INTEGER 0=Ok
1=Error
2=AngRefLow
3=Uncorrelated
-
Service value status
Table 15: TRM_12I Monitored data
Name
Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
- Analogue input module
status
Table 16: TRM_6I_6U Monitored data
Name
Type Values (Range) Unit Description
STATUS BOOLEAN 0=Ok
1=Error
- Analogue input module
status
1MRK502052-UEN B Section 3
Analog inputs
71
Technical manual