14.8.3 Function block
SPC8GAPC
BLOCK
PSTO
^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
^OUT6
^OUT7
^OUT8
IEC07000143-3-en.vsd
IEC07000143 V3 EN
Figure 363: SPC8GAPC function block
14.8.4 Signals
Table 457: SPC8GAPC Input signals
Name Type Default Description
BLOCK BOOLEAN 0 Blocks the function operation
PSTO INTEGER 1 Operator place selection
Table 458: SPC8GAPC Output signals
Name
Type Description
OUT1 BOOLEAN Command output 1
OUT2 BOOLEAN Command output 2
OUT3 BOOLEAN Command output 3
OUT4 BOOLEAN Command output 4
OUT5 BOOLEAN Command output 5
OUT6 BOOLEAN Command output 6
OUT7 BOOLEAN Command output 7
OUT8 BOOLEAN Command output 8
14.8.5 Settings
Table 459: SPC8GAPC Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
PulseMode1 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output
1
tPulse1 0.01 - 6000.00 s 0.01 0.10 Pulse time output 1
PulseMode2 Pulsed
Latched
- - Pulsed Setting for pulsed/latched mode for output
2
tPulse2 0.01 - 6000.00 s 0.01 0.10 Pulse time output 2
Table continues on next page