Table 528: Truth table for RSMEMORY function block
RESET SET OUT NOUT
0 0 Last
value
Inverted last
value
0 1 1 0
1 0 0 1
1 1 0 1
15.6.7.1 Function block
RSMEMORY
SET
RESET
OUT
NOUT
IEC09000294-1-en.vsd
IEC09000294 V1 EN
Figure 382: RSMEMORY function block
15.6.7.2 Signals
Table 529: RSMEMORY Input signals
Name
Type Default Description
SET BOOLEAN 0 Input signal to set
RESET BOOLEAN 0 Input signal to reset
Table 530: RSMEMORY Output signals
Name
Type Description
OUT BOOLEAN Output signal
NOUT BOOLEAN Inverted output signal
15.6.7.3 Settings
Table 531: RSMEMORY Group settings (basic)
Name
Values (Range) Unit Step Default Description
Memory Off
On
- - On Operating mode of the memory function
15.6.7.4 Technical data
Table 532: Number of RSMEMORY instances
Logic block
Quantity with cycle time
3 ms 8 ms 100 ms
RSMEMORY 10 10 20
Section 15 1MRK502052-UEN B
Logic
816
Technical manual