15.7.10.1 Function block
TIMERSETQT
INPUT ON
OFF
IEC14000068-1-en.vsd
IEC14000068 V1 EN
Figure 396: TIMERSETQT function
15.7.10.2 Signals
Table 578: TIMERSETQT Input signals
Name Type Default Description
INPUT BOOLEAN 0 Input signal
Table 579: TIMERSETQT Output signals
Name Type Description
ON BOOLEAN Output signal, pick-up delayed
OFF BOOLEAN Output signal, drop-out delayed
15.7.10.3 Settings
Table 580: TIMERSETQT Group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - Off Operation Off/On
t 0.000 - 90000.000 s 0.001 0.000 Delay for settable timer n
15.7.10.4 Technical data
Table 581: Number of TIMERSETQT instances
Logic block
Quantity with cycle time Range or Value Accuracy
3 ms 8 ms 100 ms
TIMERSETQT - 10 30 (0.000–90000.000) s ±0.5% ±10 ms
15.7.11 Exclusive OR function block XORQT
The exclusive OR function (XORQT) function is used to generate combinatory
expressions with boolean variables. XORQT function has two inputs and two outputs.
1MRK502052-UEN B Section 15
Logic
833
Technical manual