STRNULL is a string, fixed to an empty string (null) value
ZEROSMPL is a channel index, fixed to 0 value
GRP_OFF is a group signal, fixed to 0 value
15.10 Boolean 16 to Integer conversion B16I
15.10.1 Identification
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean 16 to integer conversion B16I - -
Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary
(logical) signals into an integer.
15.10.2 Function block
IEC07000128-2-en.vsd
B16I
BLOCK
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
OUT
IEC07000128 V2 EN
Figure 399: B16I function block
15.10.3 Signals
Table 588: B16I Input signals
Name
Type Default Description
BLOCK BOOLEAN 0 Block of function
IN1 BOOLEAN 0 Input 1
IN2 BOOLEAN 0 Input 2
IN3 BOOLEAN 0 Input 3
IN4 BOOLEAN 0 Input 4
Table continues on next page
1MRK502052-UEN B Section 15
Logic
837
Technical manual