Name of OUTx Type Description Value when
activated
Value when
deactivated
OUT11 BOOLEAN Output 11 1024 0
OUT12 BOOLEAN Output 12 2048 0
OUT13 BOOLEAN Output 13 4096 0
OUT14 BOOLEAN Output 14 8192 0
OUT15 BOOLEAN Output 15 16384 0
OUT16 BOOLEAN Output 16 32768 0
The sum of the numbers in column “Value when activated” when all OUTx (where x
= 1 to 16) are active that is=1; is 65535. 65535 is the highest integer that can be
converted by the IB16 function block.
15.12.7 Technical data
Table 598: Number of IB16 instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
IB16 6 4 8
15.13 Integer to Boolean 16 conversion with logic node
representation ITBGAPC
15.13.1 Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Integer to boolean 16 conversion with
logic node representation
ITBGAPC - -
15.13.2 Functionality
Integer to boolean conversion with logic node representation function ITBGAPC is
used to transform an integer which is transmitted over IEC 61850 and received by the
function to 16 binary coded (logic) output signals.
ITBGAPC function can only receive remote values over IEC 61850 when the R/L
(Remote/Local) push button on the front HMI, indicates that the control mode for the
operator is in position R (Remote i.e. the LED adjacent to R is lit ), and the
corresponding signal is connected to the input PSTO ITBGAPC function block. The
1MRK502052-UEN B Section 15
Logic
845
Technical manual