Name Values (Range) Unit Step Default Description
U2LowLim 0.0 - 200.0 %UB 0.1 80.0 Low limit in % of UBase
U2LowLowLim 0.0 - 200.0 %UB 0.1 60.0 Low Low limit in % of UBase
U2AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0,001% of range
Table 635: VNMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
UL1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Operation Off
On
- - Off Operation Mode On / Off
UL1ZeroDb 0 - 100000 m% 1 1 Zero point clamping
UL1Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL1RepTyp Cyclic
Dead band
Int deadband
-
- Cyclic Reporting type
GlobalBaseSel 1 - 12 - 1 1 Selection of one of the Global Base Value
groups
UL1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
UL1AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL2ZeroDb 0 - 100000 m% 1 1 Zero point clamping
UL2Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL2RepTyp Cyclic
Dead band
Int deadband
-
- Cyclic Reporting type
UL2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
UL2AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL3DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
UL3ZeroDb 0 - 100000 m% 1 1 Zero point clamping
UL3Max 0.0 - 200.0 %UB 0.1 200.0 Maximum value in % of UBase
UL3RepTyp Cyclic
Dead band
Int deadband
-
- Cyclic Reporting type
UL3LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
UL3AnDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Section 16 1MRK502052-UEN B
Monitoring
874
Technical manual